EasyManua.ls Logo

Delta VFD040EL43W - Minimum Mounting Clearance; Single Drive Installation; Side-By-Side Horizontal Installation; Zero-Stack Installation

Delta VFD040EL43W
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1 Introduction
VFD-EL-W
1-8
Minimum Mounting Clearance
(Blue arrow)
Inflow
(Red arrow) Outflow (Black) Distance
Single Drive Installation
Side-by-Side Horizontal Installation Zero-stack Installation
Model Name
Installation
Method
Minimum Distance (mm)
Temperature °C
A B C
Note 1
Max.(Derating is not
required)
Note 3
Max.(Derating is
required)
VFD002EL21W(-1)
Single Drive 120 50 - 50 60
VFD004EL21W(-1)
Side-by-Side
Horizontal
120 50 30 50 60
VFD004EL43W(-1)
Zero-stack
Note 2
- - - - -
VFD007EL21W(-1)
Single Drive 120 50 - 50
Note 4
60
Side-by-Side
Horizontal
120 50 30 50
Note 4
60
Zero-stack
Note 2
- - - - -
VFD007EL43W(-1)
VFD015EL43W(-1)
Single Drive 120 50 - 50 60
Side-by-Side
Horizontal
120 50 30 50 60
Zero-stack - - - - -
VFD015EL21W(-1)
VFD022EL21W(-1)
VFD022EL43W(-1)
VFD040EL43W(-1)
Single Drive 150 50 - 50 60
Side-by-Side
Horizontal
150 50 30 50 60
Zero-stack 150 50 0 40 50

Table of Contents