Chapter 12 Description of Parameter SettingsMS300 (High Speed Model)
12-02-19
For Example:
If the value of Pr. 02-53 displays 0003h (hex), it means RY is used by PLC.
Weights
Bit
Relay
Displayed value
Reserved
Reserved
MO1
MO2
0=Not used by PLC
1=Used by PLC
Display Memory of Frequency Command Used by External Terminal
Factory Setting: Read only
Settings Read only
When the source of frequency command set as external terminal, if Lv or Fault occurs at this time,
the frequency command of external terminal will be saved in this parameter.
EF Active when Terminal Count Value Attained
Factory setting: 0
Settings 0: Terminal count value attained, no EF display (Continue to operate)
1: Terminal count value attained, EF active
Initial Frequency Command (F) Mode after Stop
Factory setting: 0
Settings 0: By current freq. command
1: By zero freq. command
2: Refer to Pr. 02-83 to set up
Initial Frequency Command (F) Setting after Stop
Factory setting: 600.0
Settings 0.0~1500.0 Hz