Chapter 11 Summary of Parameter SettingsMS300 (High Speed Model) 
 
11-26
07 Special Parameters 
 
Pr.  Explanation  Settings 
Factory 
Setting
 
07-00  Software brake level 
230 V: 350.0~450.0 VDC 
460 V: 700.0~900.0 VDC 
370.0 
740.0 
 
07-01  DC brake current level 
0~100 %
 
0 
 
07-02  DC brake time at startup 
0.0~60.0 sec. 
0.0 
 
07-03  DC brake time at stop  0.0~60.0 sec.  0.0 
 
07-04  DC brake start frequency 
0.0~1500.0 Hz 
0.0 
 
07-05  Voltage increasing gain 
1~200 % 
100 
 
07-06 
Restart after momentary power 
loss 
0: Stop operation 
1: Speed tracking by the speed before the power loss 
2: Speed tracking by minimum output frequency
 
0 
 
07-07  Allowed power loss duration 
0.0~20.0 sec.
 
2.0 
 
07-08  Base block time 
0.1~5.0 sec.
 
0.5 
 
07-09  Current limit of speed tracking  20~200 %
  100 
 
07-10  Treatment of restart after fault   
0: Stop operation 
1: Speed tracking by current speed   
2: Speed tracking by minimum output frequency
 
0 
 
07-11 
Restart times after fault  0~10
 
0 
 
07-12  Speed tracking during start-up 
0: Disabled 
1: Speed tracking by maximum output frequency   
2: Speed tracking by motor frequency at start     
3: Speed tracking by minimum output frequency
 
0 
 
07-13 dEb function selection  
0: Disabled 
1: dEb with auto accel. / decal., the frequency will not 
return after power recovery 
2: dEb with auto accel. / decal., the frequency will 
return after power recovery 
0 
 
07-15  Dwell time at accel. 
0.00 ~ 600.00 sec.
 
0.00 
 
07-16  Dwell frequency at accel.  0.0~1500.0 Hz  0.0 
 
07-17  Dwell time at decel. 
0.00 ~ 600.00 sec.
 
0.00 
 
07-18  Dwell frequency at decel. 
0.0~1500.0 Hz 
0.0 
 
07-19 Fan cooling control 
0: Fan always ON 
1: Fan will be OFF after the AC motor drive stops 1 
minute 
2: When the AC motor drive runs, the fan is ON. When 
the AC motor drive stops, the fan is OFF 
3: Fan turns ON when the temperature attain around   
60 
o
C 
3