(5) After engine starts up, release the starter key.
Check the Oil pressure failure lamp goes off.
(6) Drive the machine for warming up the engine
for about 5 minutes at the "START / IDLING"
position of the throttle lever.
(7) After wanning up the engine, adjust the revolution
frequency to the values listed below by adjusting
the throttle handle and monitoring the revolution
counter.
Commercial frequency
Idling speed
50Hz drive
52. 5Hz (1575mm1)
6 GHz drive 62. 5H2(1875mm)
If the idling speed set above speed, frequency
becomes nearly 50Hz or 60Hz in the rated load.
(8) Set the voltage to the rated by the voltage
regulator, and turn the breaker to "ON". The
machine starts power transmission state.
-