- 22 -
5. Do not direct the exhaust towards passers-by or residences, etc.
6. If the generator is operated indoors;
• Install an exhaust pipe of sufficient diameter to let the engine exhaust gas out directly.
• Check for sufficient ventilation and position the ventilator so that the exhaust from the machine
will not be re-circulated in the room even if the ventilation is proper.
7. Check that the inner earthing system is in compliance with the local regulations.
8. Earthing the machine
• If the machine is earthed in a way different from below, follow the local rule.
• The machine is TN system which must conform to IEC 364-3 and must directly be earthed at
one neutral point.
①
Be sure to connect to earth the earthing bar connected to the PE earthing terminal.
②
Avoid earthing at the following places
1. Near underground utilities such as gas pipe, city water pipe, electric wires, underground
cables.
2. Within 2m from lightening arrester earthing place.
3. Do not use the high voltage circuit earth commonly earthing the machine.
③
Precautions in earthing
1. Drive the earthing lugs as near the machine as possible in shady and humid soil so that its
top end will sufficiently be buried inside.
2. Be sure to connect the lead-wise securely if the hanger is buried in a place of heavy traffic.
9. Also connect the load bodyworks to ground.