99
8.3 Weight and overall dimensions
Model
D*W*H (mm)
Weight (kg)
SMALLT1A0
336×144×214
6
SMALLT1A5
336×144×214
9,5
SMALLT1A10
336×144×214
13
SMALLT2A0
418×191×335
10,5
SMALLT2A5
418×191×335
18
SMALLT2A10
418×191×335
25,8
SMALLT3A0
418×191×335
11
SMALLT3A5
464×191×335
27,2
SMALLT3A10
464×191×335
32
Table 17. Dimensions and weight of the UPS
8.4 Environmental conditions
Parameter
allowable range
Operating temperature
0°C - 40°C
Storage temperature
-15°C / 45°C
Humidity
< 90%
Altitude
Below 1000 m: without changing parameters
Table 18. The conditions of storage and operation of the UPS
The performance of the UPS during the work on altitude above 1000m is:
Altitude (m)
1000
1500
2000
2500
3000
3500
4000
4500
Derating
coefficient
100%
95%
91%
86%
82%
78%
74%
70%
Table 19. UPS performance depending on height

Table of Contents