EasyManua.ls Logo

DMP Electronics 9060 - Enabling Keypad Pairing Mode; Initiating Pairing from the Panel

DMP Electronics 9060
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital Monitoring Products, Inc | 9000 Series Installation and Programming Guide 12
Step 1: Enable Pairing at the Keypad
Hold down the back arrow and CMD keys for two seconds. Enter 3577 (INST) and press
CMD. Select KPD RF (wireless survey). For more information, see Keypad Wireless Survey.
Step 2: Initiate Pairing at the Panel
Select one of the following methods to initiate pairing with the panel:
Pair Automatically (XTL Series Only)
Reset or power up the panel. For 60seconds, the panel listens for wireless keypads that
are in wireless survey and have not been programmed or paired to another panel.
Pair Manually (Any Compatible Panel Model)
Reset the panel 3times within 12seconds, allowing the panel’s Keypad Bus LEDs to turn
back on between each reset.