Digital Monitoring Products XR150/XR550 Series Installation Guide
22
INSTALLATION
17.5 FCC Registration
The Model XR150/XR550 Series complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On
the outside of the enclosure of this equipment is a label that contains, among other information, a product identier
in the format US:CCKAL00BXR550. If requested this number must be provided to the telephone company.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the
applicable FCC Part 68 rules and requirements adopted by the ACTA. See installation instructions for details.
The Ringer Equivalence Number (REN) is used to determine the number of devices that may be connected to a
telephone line. Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming
call. In most but not all areas, the sum of RENs should not exceed ve (5.0). To be certain of the number of devices
that may be connected to a line, as determined by the total RENs, contact the local telephone company.
If the XR150/XR550 Series causes harm to the telephone network, the telephone company will notify you in advance
that temporary discontinuance of service may be required. But if advance notice isn’t practical, the telephone
company will notify the customer as soon as possible. Also, you will be advised of your right to le a complaint with
the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect
the operation of the equipment. If this happens the telephone company will provide advance notice in order for you
to make necessary modications to maintain uninterrupted service.
If trouble is experienced with the Model XR150/XR550 Series, for repair or warranty information, please contact
DMP at the address and telephone number listed on the back of this document. If the equipment is causing harm to
the telephone network, the telephone company may request that you disconnect the equipment until the problem
is resolved. If your premises have specially wired alarm equipment connected to the telephone line, ensure the
installation of the panel does not disable your alarm equipment. If you have questions about what will disable alarm
equipment, consult your telephone company or a qualied installer.
Caution: To ensure proper operation, this equipment must be installed according to the installation instructions in
this manual. To verify that the equipment is operating properly and can successfully report an alarm, this equipment
must be tested immediately after installation, and periodically thereafter, according to the test instructions in
this document and the XR150/XR550 Series Programming Guide (LT-1232). Additionally, verication of Line Seize
capability should be made immediately after installation, and periodically thereafter, in order to ensure that this
equipment can initiate a call even when other equipment (telephone, answering system, computer modem, etc.)
connected to the same line is in use.
RESET and TAMPER Headers
18.1 RESET Header
The RESET header is located to the left of the EXP Expansion Header on the
right side of the circuit board and is used to reset the XR150/XR550 Series
microprocessor. To reset the panel when rst installing the system, install the
reset jumper before applying power to the panel. After connecting the AC and
battery, remove the reset jumper.
To reset the panel while the system is operational, for example, prior to
reprogramming, install the reset jumper without powering down the system.
Remove the reset jumper after one or two seconds.
After resetting the panel, begin programming within 30 minutes If you wait
longer than 30 minutes, you must reset the panel again.
18.2 TAMPER Header
The TAMPER header is for use with the optional DMP 306 Tamper Harness. The
harness connects to one or more tamper switches mounted inside the panel
enclosure to supervise against unauthorized enclosure opening or removal.
Refer to the wiring diagram on the enclosure door for correct tamper switch
wiring.
How the Tamper Works
If the enclosure is opened or removed while one or more of the system areas
are armed, a panel tamper alarm is indicated. If all areas are disarmed, a
panel tamper trouble is indicated.
Figure 12: XR550 Series Panel
Showing the RESET Jumper
Momentarily place the Reset
jumper over both of the J16
pins to reset the panel.
K
J6
J23