Doppler DLC - 9 817 - 818 Are Open

Default Icon
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Go to Table
of Contents
9 817 - 818 Are Open
Up and down limit inputs (817=0 and 818=0) are both
open simultaneously.
Cause
Troubleshooting
1. Check the condition of the pre-limit switches. Press UP left
arrow in the main PCB and locate 817-818. Star indication is
showing the condition. In a middle floor both prelimits must
stay active if the limits hit the mechanical Cam, then Star sign
must disappear.
TIP: Check electrical drawings pages 4-12-13