EasyManua.ls Logo

DSC HS2128 - Page 88

DSC HS2128
261 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 6: Programming
121-124 – Command Output 1-4
01 – True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
02 – Timed Output / Latched Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
03 - Access Code Required / No Code Required
ON: access code required for activation.
OFF: no access code required for activation.
129 – Partition Status Alarm Memory
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
132 – Holdup Output
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
146 – TLM Alarm
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
147 – Kissoff Output
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
148 – Ground Start
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: active during normal operation. Deactivated when triggered.
149 – Alternate Communicator
01 – True Output/Inverted
ON: deactivated during normal operation, activated when triggered.
OFF: activated during normal operation, deactivated when triggered.
02 – Timed Output / Latched Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
04 – Fire Alarm
ON: activates with fire alarm, [F] key, fire zones, 2-wire smoke.
OFF: does not activate with fire alarm.
- 88 -