17
105.4 Battery Cabinet Voltage Check and DC Fuse Installation
Note:Thisprocedureappliestoa36batterysystem.Fewerstepsmayberequireddependingonthenumberof
batteries in the system.
Important: Always observe proper polarity when taking battery voltage measurements.
1. Usingadigitalvolt-ohmmeter(DVM),checkforcorrectnominalbatteryvoltagebetweenrightsideoffuseblock
F1andleftsideofbatterycabinetterminalblockTB2(NEG-).Checkforcorrectvoltageineachbatterycabinet.
2. Identify the battery cabinet furthest from the inverter and install battery Fuse F1. Observing proper polarity, use
DVMtocheckforcorrectbatteryvoltagebetweenbatterycabinetterminalblockleftsideTB2(NEG-)andTB4
(POS+).Inaneightbatterysystem,proceedtoSection105.5.
3. Identify next battery cabinet in line. Observing proper polarity, use DVM to check for correct battery voltage be-
tweennextbatterycabinetterminalblockleftsideTB1(NEG-)andTB3(POS+).
4. Install battery Fuse F1. Observing proper polarity, use DVM to check for correct battery voltage between battery
cabinetterminalblockleftsideTB2(NEG-)andTB4(POS+).Ina16or24batterysystem,proceedtoSection
105.5
5. Identify last battery cabinet in line. Observing proper polarity, use DVM to check for correct battery voltage be-
tweenlastbatterycabinetterminalblockleftsideTB1(NEG-)andTB3(POS+).
6. Install battery Fuse F1. Observing proper polarity, use DVM to check for correct battery voltage between battery
cabinetterminalblockleftsideTB2(NEG-)andTB4(POS+).
105.5 Electronics Cabinet Voltage Check
Usingadigitalvolt-ohmmeter,checkforcorrectnominalbatteryvoltagebetweenelectronicscabinetDCInputNEG
and POS terminal blocks. Refer to table in section 105.3 for proper system DC voltage.
BatteryTerminalTorqueSpecications
Type "S" Batteries
Battery Part No. Torque
93012367 30 inch-lbs.
93012368 30 inch-lbs.
93012369 110 inch-lbs.
93012370 110 inch-lbs.
93012371 110 inch-lbs.
93012372 110 inch-lbs.
Type "G" Batteries
See battery label
Type "N" Batteries
Battery Part No. Torque
0120881, 882 66 inch-lbs.
0120883, 884 177 inch-lbs.
0120885, 886, 265 inch-lbs.
887, 888
Caution: Torque all connections in accordance with the following tables.
Failure to do so may create an unsafe condition or fire hazard.
Battery Fuse Block
275 inch-lbs.
Battery Fuse
120 inch-lbs.