36
300.2 Routine System Maintenance
TheLSNinvertersystemunitisdesignedtoprovideyearsoftrouble-freeoperation.Itsself-testing/self-diagnostic
microprocessor will check the batteries and inverter regularly to ensure proper operation.
Theunitdoesrequiresomeroutineattentiontoassurepeakperformance.Dual-LiterecommendsaPreventative
Maintenancecheckbeperformedbyaqualiedservicetechnicianatleasteverysixmonths.Thetechnicianmust
observeimportantsafetyprecautionswhileperformingthefollowingrecommendedtasks:
• Inspect and clean the unit interiors;
• Inspect and record any Alarm and Inverter Logs;
• Inspect all batteries for leaks, case swelling or terminal corrosion;
• Check the AC and DC meter functions and recalibrate if necessary;
• Perform an emergency operation test to check operation of all critical connected loads;
• Check the values of metered parameters and system logs,
• Change air lters (see below).
NOTE: If the LSN unit is installed in an area where audible alarm signals may not be
heard, a weekly visual check is advised.
300.3 Changing Air Filters
CAUTION
ThisproceduremustbedonebyaqualiedservicepersonONLY!
Basedontheinstallationenvironment,LSNinvertersystemairltersshouldbechangedatleasteverysixmonthsto
assuresufcientairowtopreventoverheatingofunitelectronics.
Tochangeunitairlters,followthesesteps:
1. Follow the steps in Section 207.1 to safely shut down the unit. Remember to leave the system door closed for at
least veminutestoallowcapacitorstodischarge.
2. Afterveminuteperiod,openthesystemdoor.
2. Removeoldlterswhichareheldinplacebydouble-sidedadhesivetape.
3. Clean off any tape adhesive residue from back of door.
4. ReplaceltersusingDual-LiteFilterKit
5. Close the system door.
6. Follow the “System Startup Procedure” outlined in Section 109. Be sure to complete all of the steps to assure the
unit will operate properly.