EasyManua.ls Logo

DualLite LSN - 201.6 How to Change Operating Modes

DualLite LSN
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
User Keypad Actions Display Readout
[PRG] EnterControlCode
Setup Value
0 Enter Control Code
Setup Value 0
[ENT] PasswordRequired
Please enter 6-Digit user password
****** EnterControlCode
Setup Value 0
[ENT] Time14:00:00
EnterTime(HH:MM:SS)__:__:__
093000[ENT] Time14:00:00
Enter Time(HH:MM:SS)09:30:00
IMPORTANT: The"TIME"(parameter0)and"DATE"(parameter10)mustbesetbyuserinorderforsystemto
operate properly.
201.5 How To Change Operating Modes
Therearefouravailableoperatingmodes:
1. Off = System Off
2. Line = AC Pass-Through
3. Auto = Standby Operation
4. On =InverterOn(EmergencyBatteryOperation)
The LSN inverter system will select the appropriate operating mode automatically upon start-up.
NOTE: Changing the operating mode may prevent the LSN system from operating during a power failure.
To change the system operating mode to Inverter Mode,followthesesteps:
1. Press [PRG]
2. Enter the parameter number “150”
3.Entertheuserpassword(ifnotalreadyactive)
4. Press [ENT]
5.Enterthedesiredoperatingmodeidentierandpress[ENT]
User Keypad Actions Display Readout
[PRG] Enter Control Code
setup value
150 Enter Control Code
setup value 150
[ENT] PasswordRequired
Please enter 6-digit user password
****** Enter Control Code
setup value 150
[ENT] User Inverter Mode Control Menu
Off(1)Line(2)AUTO(3)On(4)
4 [ENT] Inverter Line Command Sent
Off(1)Line(2)AUTO(3)On(4)

Table of Contents