40
Param. Keyboard Password
No. Type Alpha Level Description
0 Both t User Time
1 Dsp vi N/A InputVoltage
2 Dsp vo N/A OutputVoltage
4 Dsp o N/A OutputCurrent
5 Dsp va N/A Volt-AmpsOut
6 Dsp ib N/A BatterySuppliedCurrent
7 Dsp vb N/A BatteryVolts&ChargingCurrent
8 Dsp vi N/A InputFrequency
9 Dsp rt N/A RunTimeRemaining
10 Dsp d User Date
11 Dsp at N/A AmbientTemperature
12 Dsp st N/A HeatsinkTemperature
14 Dsp xt N/A TransformerTemperature
15 Both id User Unit ID string.
Remoteentryonly(20char)
16 Dsp l N/A PercentofFullLoad
17 Dsp w N/A WattsOutput
18 Dsp pf N/A OutputPowerFactor
19 Both val Serv High VA Overload alarm setpoint
20 Dsp po N/A PowerOutages
21 Dsp ol N/A Overloads
22 Both sh Fact SystemHoursDisplay/Reset
23 Both im Fact InverterMinutessincestartup/Reset
24 Dsp il N/A InverterLog
25 Dsp al N/A AlarmLog
26 Dsp tr N/A TestResultsLog
27 Dsp cf N/A CrestFactor
28 Both bl Serv Brownout Level
30 Both mind N/A MinimumDCvoltssincestartup
31 Both maxd N/A MaximumDCvoltssincestartup
32 Both minvi N/A MinimumACinputvolts
33 Both maxvi N/A MaximumACinputvolts
34 Both minvo N/A MinimumACoutputvolts
35 Both maxvo N/A MaximumACoutputvolts
36 Both minva N/A MinimumoutputVA
37 Both maxva N/A MaximumoutputVA
40 Both sn Fact Factory Serial Number
42 Dsp nf N/A NominalFrequency
43 Both nvi Fact Nominal Input Voltage
44 Both nvo Fact Nominal Output Voltage
45 Both rva Fact Rated VA
46 Both rw Fact Rated Watts
51 Both lf Serv LowInputFrequencyswitchpoint
52 Both hf Serv HighInputFrequencyswitchpoint
59 Both lvoa Serv Low Output Volts alarm setpoint
60 Both lvos Serv Low Output Volts shutdown setpoint
61 Both hvoa Serv High Output Volts alarm setpoint
62 Both hvia Serv High Input Volts alarm setpoint
65 Both lb Serv Low Battery Volts alarm setpoint
66 Both nlb Serv Near Low Battery volts alarm setpoint
67 Both hb Serv High Battery volts alarm setpoint
Param. Keyboard Password
No. Type Alpha Level Description
68 Both lr Serv Low Run Time alarm setpoint
73 Both tt User Time of Day for Monthly test
78 Both ae Diag AlarmShutdownE/D
80 Both ats Serv High Ambient Temp alarm setpoint
81 Both ats Serv High Ambient Temp shutdown setpoint
82 Both hta Serv High Heatsink Temp alarm setpoint
83 Both hts Serv High Heatsink Temp Shutdown setpoint
84 Both xta Serv High Transformer Temp alarm setpoint
85 Both xts Serv High Transformer Temp Shutdown
setpoint
89 Both ird User Inverter Active Relay Delay
95 Both cb Serv Console Baud Rate
110 Both cvin Fact ACVinGain
111 Both cvid Fact AC V in Offset
112 Both cvon Fact ACVoutGain
113 Both cvod Fact AC V out Offset
114 Both caon Fact ACAmpsOutGain
115 Both caod Fact AC Amps Out Offset
116 Both cdvn Fact DCVoltsGain
117 Both cdvd Fact DC Volts Offset
118 Both cdan Fact InverterCurrentGain
119 Both cdad Fact Inverter Current Offset
120 Both ccn Fact ChargerCurrentGain
121 Both ccd Fact Charger Current Offset
122 Both ct Fact Charger Type
123 Both mc Fact Charge Current Setpoint Number
124 Both lcv Fact Batt Chg Lower On Volts
125 Both fcv Fact Battery Reduced Float Volts
126 Both hcAv Fact Batt Chg Upper Off Volts
127 Both mtd User Date for Monthly test
128 Both mtd User Date for Monthly test
129 Both mtt Fact Monthly Test Time Duration
130 Both att Fact Annual Test Time Duration
137 Dsp sv N/A SoftwareVersion
150 Prg inv User Inverter off, line, auto, on
151 Both lre Serv E/DLowRunTimeAlarm
152 N/A N/A N/A ReservedForFactoryUse
153 Dsp op N/A CompileOptions
154 Dsp sl N/A Servicelog
155 Dsp bvl N/A Batteryvoltslog
156 Dsp bdl N/A Batterydischargevoltslog
157 Dsp pl N/A Powerlog
158 Dsp pvl N/A Peakvalueslog
159 Prg tled Diag LED relay diag test
160 Prg clr N/A Clrpeakvalues
161 Dsp drl N/A DiagnosticReportLog
162 Both ibe N/A InverterbeepOn/Off
163 Both edw User E/DWeeklyTest
164 Both lfa Serv LowInputFreqAlarmsetpoint
165 Both lfe Serv Enable/DisableLowInpFreqAlm
166 Both lvoe Serv E/DLowOutputVoltsAlarm
167 Both lvse Serv E/DLowOutputVoltsShutdown
Appendix 1.
Parameter“HotKey”NumericalListing