Alarm Message What it means What to do
ALM VA Hi 16218 15000 Unit has detected an Remove some of the load until alarm clears.
overload and is about to
shut down.
ALM I2C Comm Microprocessorfailure. ContactDual-Lite’sTechnical Support Center.
ALMBattVHi182177 Batteryvoltageistoo ShutdowntheunitandcontactDual-Lite’s
high. Technical Support Center.
ALM BattV Lo 125 127 Battery voltage is too If charger light is on, allow condition to persist
low. If unit is in Inverter for 24 hours. If alarm does not clear, contact
modeitisabouttoshut Dual-Lite’sTechnicalSupportCenter.
down.
ALM BattV Nr Lo 130 132 Battery voltage is near Same as above.
Low level.
ALM AmbT Hi 62C 60C Ambient temperature If unit is located is a hot environment, relocate
withintheelectronics Ifnot,contactDual-Lite’sTechnicalSupport
Center.
ALM CktBrkr Trip One or more output Locate tripped breaker and reset. If it trips
circuit breaker has again check load circuit for shorts.
tripped.
LCLSHTDNXfmrTHi Systemhasshutdown ContactDual-Lite’sTechnicalSupportCenter.
because output
transformer has overheated.
LCLSHTDNHtsnkHi Systemhasshutdown ContactDual-Lite’sTechnicalSupportCenter.
because inverter
heatsink has overheated.
LCL SHTDN AC Out Over System has shut down Reduce load.
Current due to high output current.
SHTDN VA Ovrld 23110 System has shut down. Reduce load.
22500 Overload is greater than
50%oftheratedoftheunit.
SHTDN VA5 Ovrld 19111 System is overloaded by Reduce load.
18000 atleast20%.Ithasbeen
in this condition for 5
minutes and then shut down.
SHTDN VA10 Ovrld 17200 System is overloaded by Reduce load.
16500 atleast10%.Ithasbeen
in this condition for 10
minutes and then shut down.
SHTDNACVoutLo187192 Systemhasshutdown ContactDual-Lite’sTechnicalSupportCenter.
due to low AC output voltage.
SHTDNXfmrTHi122C120C Systemhasshutdown ContactDual-Lite’sTechnicalSupportCenter.
due to transformer overheating.
SHTDNAmbTHi82C80C Systemhasshutdown ContactDual-Lite’sTechnicalSupportCenter.
due to overheating in the
electronics cabinet.
SHTDNHtsnkHi123C120C Systemhasshutdown ContactDual-Lite’sTechnicalSupportCenter.
due to overheating if the
inverter heatsink.
ALM Battery Charger Failure Chargerisnotfunctioning. ContactDual-Lite’sTechnical Support Center.
ALM Annual Test Failed System failed the 90-minute Some of the batteries may have failed.
annual test Run a manual discharge and evaluate battery
performance. Call Dual-Lite's Technical
Support Center.
ALM Monthly Test Failed System failed the monthly Some of the batteries may have failed.
5-minute test Run a manual discharge and evaluate battery
performance. Call Dual-Lite's Technical
Support Center.
Weekly Test Failed System failed the 1-minute test May have been caused by a decrease of more
than10%oftheconnectedload.Loadchange
message will appear at parameter #26. Check
connected load and address any issues
accordingly.