9
ANTI-BLINDING
Alert function in case of disturbing radio transmission (radio blinding attempts).
In case of blinding, the receiver alerts with a “Blinding” message on display and activating the output LWB.
ENTRY TIME
Delay time before consider alarm after – at receiver armed – a violation of the zones 1 ÷ 10.
If – after this time – the receiver is not disarmed, then starts alarm.
Values:
00 seconds (instantaneous zones, no delay)
10 seconds
20 seconds
30 seconds
EXIT TIME
Time available to leave the protected zone without alarms after the arming command to the receiver. During this time the receiver does not
consider alarm if the radio zones are violated.
Values:
5 seconds
60 seconds
RELAY MODE FOR OPENED DOOR (P.A.INS = YES / NO)
Set the behaviour of zone alarm relay output when – at the arming of the receiver – a zone is opened. This function can be used only if the
“Door Control” option is enabled.
FOLLOW ZONE (P.A.INS = YES): maintain the zone relay output opened until the zone stays opened
NORMAL (P.A.INS = NO): the zone relay output is impulsive. The relay temporary opens then closes after some seconds (even
if the zone stays opened). At the end of Opened Door signalization the relay closes
In both cases, giving a +12 V on RESET input, the zone relay opens to alert that there is a opened door. After some seconds the zone relay
output closes bypassing the zone.
SUPERVISION
Max time before consider the radio zone as “missing”. Each time the radio zone sends any radio code, the receiver restart the countdown.
Values:
4 hours
8 hours
12 hours
NO (Supervision off)
P OUTPUT
Set the behaviour of the programmable P output. The output switches for these events:
Partial Arming
Missed Supervision