36
9.1 Fill Boiler With Water And Purge Air
NOTICE
To maintain boiler effi ciency and prevent boiling
inside the heat exchanger, fl ush entire heating
system until clean.
• Flush heating system, including all heating zones.
• Fill boiler with potable water.
•
Fill boiler and system piping with water (or
antifreeze-water solution, if used). See antifreeze
information page 13. Purge air from boiler using air
vent. Purge air from system piping.
•
Inspect system piping and boiler connections. Repair
any leaks immediately.
•
Activate all heating zones and calls for heat,
including CH calls and DHW calls (if available).
•
Close manual gas shut off valve. Let system run for
30 minutes. When boiler goes into lockout, reset
boiler by pressing "Reset" button until boiler resets.
•
Do not open gas shutoff valve until all air is purged
from system.
9.2 Fill Condensate Trap with Water
•
Disconnect spring tension clip from condensate hose
barb. See fi gure 9-1.
•
Disconnect tubing below from hose barb.
•
Pour approximately 2 cups (473 ml) of water into
condensate drain.
•
Reconnect tubing to hose barb with spring tension
clip. See fi gure 9-1.
FIGURE 9-1 Condensate Drain Assembly
NOTICE
IMPORTANT: Condensate trap must be manually
fi lled with water at initial start up.
.
2. Reconnect hose to hose
barb with spring tension clip
before starting boiler.
1. Disconnect spring tension
clip from hose barb and fi ll
Condensate trap with water.
9 - START UP PROCEDURE