15 - RATINGS AND CAPACITIES
PN 240012787 Rev. C [11/15/2020]
Table 2 - Ratings and Capacities
Boiler
Model
Number
of
Sections
(1)
Input
Btu/hr
(1)
Heating
Capacity
Btu/hr
(2)
Net AHRI
Rating Water
Btu/hr
AFUE
Flue
Diameter
Inches
(1)
High
Altitude Input
Btu/hr
(3)
Recommended
Air Cushion
Tank
DXL-060K 3 59,000 50,000 43,000 84.0 4 53,100 15
DXL-095K 4 92,500 78,000 68,000 84.0 5 83,200 30
DXL-120K 5 120,000 101,000 88,000 84.0 6 108,000 30
DXL-150K 6 149,000 125,000 109,000 84.0 6 134,100 30
DXL-XXXK 7 175,000 147,000 128,000 84.0 7 157,500 30
DXL-XXXK 8 205,000 172,000 150,000 84.0 7 184,500 30
DXL-235K 9 235,000 197,000
171,000
84.0 7 211,500 30
EXPLANATORY NOTES

-- Recommended chimney height 20 feet. In special cases where conditions permit, chimney height may be
reduced to 10 feet. Refer to the latest revision of National Fuel Gas Code ANSI Z223.13/NFPA 54 part 11.
-- Electric service to be 120 Volts, 15 Amps, 60 Hz.
-- The MEA number for the this boiler is 19-79-E.
(1) Input rating for sea level to 2,000 ft. (610m) above sea level.
United States, over 2000 ft (610m) above sea level. Reduce input rate 4% for every 1000 ft (304m) above sea
level.
(2) Net AHRI Water Ratings shown based on piping and pickup allowance of 1.15. Consult manufacturer before selecting
boiler for installations having unusual piping and pickup requirements, such as intermittent system operation,
extensive piping systems, etc.
For forced hot water systems where boiler and all piping within area to be heated, boiler may be selected on basis of
its heating capacity.
(3) Tank sized for non-ferrous baseboard or radiant panel systems. Increase size for cast iron baseboard and
radiation.
STANDARD EQUIPMENT: Boiler Jacket, Cast Iron Boiler Battery, High Limit Control, Intermittent Electric Ignition Pilot

Pilot Flow Adjustment, Pilot Filter), A.S.M.E. Relief Valve, Drain Valve, Spill Switch, Rollout Switch, Automatic Vent Damper,
Wiring Harness, Safety Pilot.