EC5000
Description of Functional Parameter
EC5000
Description of Functional Parameter
- 84 - - 85 -
Read only, display AC drive power grade
0total total time of accumulative when AC drive is power on
1total time of accumulative when AC drive is running
C30 power selection factory defaut*3
C31 time select setting limits0 1 factory defaut1
When C32 is selected to be action total time, set C32 to be time with unit of
1 hour,and calculate time from then on.
C32 timer L setting limits0H 9999H factory defaut0H
C33 timer H setting limits027*10000H factory defaut0H
Set output missing test time
C29 SPO delay setting limits0.0S2.0S factory defaut0.2S
When the AC drive is running above the reference frequency, it’s in the filed
weaking control area, at this time, if the torque force is not enough, it’s
necessary to start frequency reduction compensation to increase the torque.
0: OFF 1: ON
C34 Frequency reduction compensation setting limits: 0 1 factory defaut: 1
After the operation signal is given, a delay function is added. When the
user uses AC drive to power on and operate directly, the time delay of 0-15s
can be set.
C35 Frequency reduction time setting limits: 0H 9999H factory defaut: 11.0S
C36 Operate delay time setting limits015S factory defaut0
D01 PID selection setting limits0 3 factory defaut0
0without PID control
1with PID control(D controls deviation)
2with PID control(D controls feedback value)
3with PID control(feedback value is in opposite direction)
1.voltage signal of control circuit terminal FV(0-10): select(A03) to be 2 or 3
to set running direction.
2.frequency order data(A27-A34): select(A03) to be 0 or 1 to set running
direction (combination of multi-function joint, multi-pace speed order and jog/
start order)
Set feedback value
Use current signal(4-20mA) or voltage signal(0-10V) of control circuit
terminal to set feedback value.
1.Current signal of control circuit terminal FI: select(B15) to be 1 to set FI
function.
2.Voltage signal of control circuit terminal FI: select(B15) to be 0 to set FI
function (set PC board SW1-1to be OFF)
Set target value
EC5000 AC drive can select several target value. Use voltage signal of
control circuit terminal FV or frequency order data A27-A34 to set target value.
D02 feedback increase setting limits0.00 10.00 factory defaut1.00
D03 propotion increase setting limits0.0 10.0 factory defaut1.0
D04 integral time setting limits0.0S 100.0S factory defaut10.0S
D05 differential time setting limits0.00S1.00S factory defaut0.00S
D06 PID deviation setting limits-109%109% factory defaut0%
D07 integral limits setting limits0% 109% factory defaut100%
D08 wave filting time setting limits0.0S2.5S factory defaut0.0S
Feedback increasesmall adjustment for PID feedback test value.
Proportion increaseset P control proportion increase. If set to be 0.0, no P
control.
Integral timeset I control proportion increase. If set to be 0.00, no I control.
Differential timeset D control proportion increase. If set to be 0.0, no D control.
PID deviationdeviation adjustment to frequency order control by PID, with
unit of 1%.
Integral limitsset the up limits value of frequency output controlled by I, with
unit of 1%.
Wave filting timeset the one time delay data of frequency order controlled by
PID