- 92 - - 93 -
Description of Functional Parameter
5
Only LCD manipulator has this functional code
0: setting frequency
1: output frequency
2: output current
3: output voltage
4: output power
5: voltage EDC
6: feedback PID
Pr-F14 monitoring select setting limits:0~11 factory default:0
Only LED manipulator has this functional code
0:setting frequency
EC5000
Description of Functional Parameter
F15 Language Selection setting limits: 0~1 Default default: 0
1:output frequency
2:output voltage
3:output current
4:output power
5:voltage EDC
6:feedback PID
7:temperature
8:S terminals functional
9:Y terminals functional
10:running time
11:version ROM
Only LCD manipulator has this functional code
0:Display Chinese
1:Display English
Pr-F15 LED Display sel Range:0~3 factory default:0
Only LED manipulator has this functional code
0:seven items for monitoring:(Fset、 Fout、 Vout、 Aout、 KVA、
EDC、PID)
1:increase two external terminals S1-8 and Y1-4 for monitoring the
input and the output
2:increase three items for monitoring:TEP、 HOU、 the VER of
mother board
3:increase five items which monitored above 1&2
F16 Low-speed sel(Pr_F15) setting limits:0~2 factory default:0
Set the input voltage of the AC drive. According to this set value, the
AC drive can switch the voltage protection level.
0:Free running;
1:Running at A16(start freq)
2:Running at Zero-speed.
F17 Zero-speed increase(Pr_F16) setting limits:0~100% factory
default:50%
According to the rating current of 100% set the output current at zero
speed
F18 Motor tuning(Pr_F17) setting limits:0~2 factory default:0
0:no auto tuning;
1:static auto tuning(Suitable for use in already connected load
motor);set the F18 to be 1,and start the ac motor drive can realize the
measure of the stator resistor.
2:Dynamic auto tuning(Suitable not connected to the load of the
motor) blongs to the stator resistance type self-learning and no-load
current type study, through self-learning between resistance and no-load
current of the motor can be obtained, the test motor running at rated
frequency.
F19 E l e c t r i c al l e aka g e ( P r _ F 1 8) set t i n g l i m i ts :0~ 4 0 % f a c t o r y
default:18%
With motor set by 100% of the rated voltage for motor voltage which
is caused by the leakage inductance of the amount of pressure drop
F20 AVR(Pr_F19) setting limits:0~1 factory default:1
0:NoAVR;
1:AVR;
F 2 1 B r a k f r e q u e n c y ( P r _ F 2 0 ) s e t t i n g l i m i t s : 0 ~ 5 0 . 0 0 H z f a c t o r y
default:0.0Hz
0.00Hz The function is invalid.
0.1~50Hz When the stop order is given, DC injection braking when
deceleration to the set frequency.