16
Low voltage of battery setting
LCD display Settings
The battery voltage selecting interface. You may choose the
following output voltage:
9.8: Low voltage of battery is 9.8Vdc
9.9: Low voltage of battery is 9.9Vdc
10: Low voltage of battery is 10Vdc
10.2: Low voltage of battery is 10.2Vdc
10.5: Low voltage of battery is 10.5Vdc
dEF (default): EOD voltage automatically varies with loads,
including 21.5 hours discharge protection
Bypass mode setting
LCD display Settings
Enable or disable Bypass function. You may choose the
following two options:
ON: Bypass enable
OFF (default): Bypass disable
AUO setting
LCD display Setting
AUO setting only can be set in Stdby mode or Bypass mode.
You may choose the following two options:
ON: UPS will start up automatically and works in Line mode
when connect mains.
OFF
(Default): UPS won’t start up automatically when
connect mains except EOD, it will work in standby or bypass
mode.