1) What are the requirements/equipment needed to connect into Boot Loader mode?
a. Ethernet Cable
b. RS-485 connection. If PC does not have COM port, you may need a USB to Rs-485
converter.
c. Telnet program. For Windows XP user, the built-in hyper terminal is good enough.
2) How to get into EasyIO-30P’s boot loader mode?
Boot loader can be connecting via Ethernet or Serial COM.
Please refer to document EasyIO Basic 01 - Firmware Flashing User Guide.
3) What are the settings for EasyIO-30P’s bootloader mode?
Please refer to document EasyIO Basic 01 - Firmware Flashing User Guide.
4) What is the IP address for EasyIO-30P Boot Loader mode?
The default IP address for EasyIO-30P boot loader mode is 192.168.10.10.
This IP address is not the same with the web browser IP address. If user has changed the
username and password via web browser, that username and password cannot be used for boot
loader mode.
5) For Windows Vista or Windows 7, the third-party hyper terminal software can be used
to communicate with EasyIO-30P?
Yes. You can use any telnet program that is available.
6) If the login name and password was changed at the EasyIO-30P web server, does this
affect the boot loader’s login name and password?
No. The login credentials for web browser and boot loader is different. The login credentials for
terminal mode and web browser is the same.