EasyIO 30P – Frequently Asked Questions
7
Frequent Ask Questions – DDC: Main Plant Control, AHU
Control and Unitary control
Related to EasyIO-30P series, EasyIO-DEM-5 and EasyIO-LT-D5
General
1) What is the power consumption for EasyIO products?
All EasyIO products’ power consumption is stated in all of our catalogues. For further details,
please refer to our products catalogue.
2) Can EasyIO-30P share 24VAc transformer with non EasyIO products?
It is not advisable to share transformer with EasyIO products, as our power supply are half wave
power supply.
3) Can EasyIO-30P share transformer with EasyIO-DEM-5?
Yes. Please mind the polarity. Make sure the 24G and 24H are correct.
4) How many EasyIO-30P can be connected to a 2A transformer?
As per our power rating, a 2A transformer can power up to 6 EasyIO 30P. Each EasyIO30P’s peak
power consumption with full load is at 320mA @ 24VAC.
5) What protocol does EasyIO-30P support?
EasyIO-30P supports BACnet, Modbus and Sedona.
Getting Started – Hardware
1) What input type does a Universal Input (UI) support?
EasyIO 30P supports Voltage Free Contact as digital input