EasyIO 30P – Frequently Asked Questions
19
1) What are the requirements/equipment needed to connect into Terminal mode?
a. RS-485 connection. If PC does not have COM port, you may need a USB to Rs-485
converter.
b. Telnet program. For Windows XP user, the built in hyper terminal is good enough.
2) How to get into EasyIO-30P’s terminal mode?
Terminal mode only can be connected via serial COM. A RS-485 converter would be needed if
hardware does not support RS-485 communication.
3) What are the settings for EasyIO-30P’s terminal mode?
Please refer to document EasyIO Basic 03 - Terminal Mode User Guide.
4) Why can’t get into EasyIO-30P’s terminal mode? BACnet firmware is using.
If you are running EasyIO-30P with BACnet firmware , most likely the RS-485 COM is
broadcasting BACnet MS/TP messages. This will jammed up the RS-485 port when trying to
connect via RS-485.
You need to disconnect the RS-485 cable at the controller, get into boot loader mode then only
connect the rs-485 cable to the controller.