6.6 UPS remote control functions
Connectivity cards
Connectivity cards allow the UPS to communicate in a variety of networking environments and with differenttypes of
devices. The5PXmodels have one available communication bay for the following connectivity cards:
Gigabit Network card(Network-M2) : provides a Gigabit Ethernet connection and enables secure UPS monitoring
over HTTPS web browser interface, SNMP v1/v3 protocol and email alarms. In addition, up to 3 Environmental
Monitoring Probes can be attached to obtain humidity, temperature, smoke alarm, and security information.
Industrial Gateway card(INDGW-M2) :Provides Modbus RTU and Modbus TCP communication support in addition
to the same secure UPS monitoring, management and sensor capability as the Gigabit Network card.
Relay-MS card: provides isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPS
alarm/OK, or on Bypass.
INDRELAY-MS : The Industrial relay Card-MS (INDRELAY-MS) provides a simple way to remotely input UPS information
to an alarm system, PLC or a computer system via dry contacts. It offers five isolated dry contact outputs and one
isolated dry contact input.
Programmable signal inputs
The 5PX incorporates several programmable signal inputs: oneRemote Power Off (RPO) input terminal, one RemoteOn/
Off (ROO) input terminal, one RS-232 input (pin-4).
Signalinputs can be configured (see Settings > Comm settings > Signal Input) to have one of the following functions:
Function Description
No No function. (Please choose a function if you want to use input signal.)
RPO Remote Power off (RPO) is used to shutdown the UPS remotely.
ROO
Remote On/Off allows remote action of a button or other interface to switch On/
Off the UPS. (Cold start is prohibited while using the ROO function.)
Building alarm
Active input generates an alarm “building alarm”.