All models Normal mode Battery mode
Short circuit current limitationin battery
mode
Model
Current
limitation
1000 31A
1500 38A
2200 38A
3000 64A
Transfer time
Utility Outage: 1-4ms for normal mode, >5ms for sensitive mode
Utility abnormal: <10ms for normal mode ,<25ms for sensitive mode
10.7 Electrical output connection
Catalog Number
Output conection
Output cable
5PX1000IRT2UG2 (4) IEC10A Primary group
(2) IEC10A Group 1
(2) IEC10A Group 2
(2) IEC10A
5PX1500IRT2UG2
5PX2200IRT2UG2
(4) IEC10A + (1) IEC16A Primary group
(2) IEC10A + (1) IEC16A Group 1
(2) IEC10A Group 2
5PX2200IRT3UG2
5PX3000IRT2UG2
5PX3000IRT3UG2
10.8 Battery
Internal batteries EBM
Specifications
1000VA: 48Vdc - 4 x 12V, 7Ah (9Ah max)
1500VA: 48Vdc - 4 x 12V, 9Ah
2200VA: 72Vdc - 6 x 12V, 7Ah (9Ah max)
3000VA: 72Vdc - 6 x 12V, 9Ah
5PXEBM48RT2UG2: 48Vdc - 2 x 4 x 12V, 2 x 9Ah
5PXEBM72RT2UG2: 72Vdc - 2 x 6 x 12V, 2 x 9Ah
5PXEBM72RT3UG2: 72Vdc - 2 x 6 x 12V, 2 x 9Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-5 year float service life at
25°C (77°F).
Monitoring Advanced monitoring for earlier failure detection and warning
EBM battery cable
length
2U EBM cable length:350mm/13.78in
3U EBM cable length:530mm/20.87in