10.9 Environmental and safety
Standards
IEC/EN 62040-1:2008+A1:2013
EN IEC 62040-2: 2018
IEC 62040-2: 2016
FCC CFR Title 47, Part 15, Subpart B
IEC/EN 62040-3
IEC 62040-1:2017
UL1778 5th edition
CSA 22.2
EMC (Emissions)
EN IEC 62040-2: 2018 C1
EN 62040-2: 2006 C1
IEC 62040-2: 2016 C1
EN 55011:Class B
CISPR11 Class B
CISPR32 Class B
FCC part 15 Class B
EMC (Immunity)
IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): 4 kV
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common Mode
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
Agency markings
CE, cTUVus, EAC, Cm, Ukr, UKCA,
KC (only on 5PX1500IRT2UG2, 5PX2200IRT2UG2, 5PX3000IRT2UG2,
5PX3000IRT3UG2)
Operating temperature 0 to 40 °C (32 to 104 °F)
Storage temperature -15 to 50°C (5 to 122 °F)
Relative humidity 20 to 90 % (without condensation)
Operating altitude
Up to 3,000 meters (9,843 ft) above sea level, no derating for 40°c
(104°F) room temperature
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise
Line mode:<40dB Buck/boost mode:<45 dB
Batt. Mode: <45dB, 50dB for 3K
11 Glossary
AVR
The Automatic Voltage Regulationmaintains a constant voltage level for
electrical equipment loads when the voltage falls outside the voltage tolerance
range.
Backup time
Time during which the load can be supplied by the UPS operating on
batterypower.
EBM
Extended Battery Module