106 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
Table 25. Parts of the Touchscreen (Continued)
D
The Navigation Menu allows selection of system information, control, events screens and other display functions by
touching the menu buttons. (See Table 26).
Settings Overview Timeline Meters Control
NOTE You can also access screen selections from the menu drop-down on the Header Bar.
Touching an area on the screen that requires a password shows a locked padlock icon with the required
security level number. (see Table 24).
77..33..22 UUssiinngg tthhee NNaavviiggaattiioonn MMeennuu BBuuttttoonnss
The Overview Screen menu bar shown in Figure 64 allows you to display data in the information area to help
you monitor and control UPS operation. Table 26 shows the basic menu structure.
Table 26. Navigation Menu Map
Menu Option Description
Overview
Displays the power map of the UPS with colors indicating the power flow (online, ESS or bypass mode). Also
displays data pertaining to system load and efficiency
Timeline
Displays the list of active system events and a historical log of system events. Historical logs include a
detailed time stamped list of over 300 events. Events include detailed information including the description,
source, type and solution.
Meters
Displays performance meters for the system or critical load. When selected, the front display shows
individual screens of input parameters, output parameters or bypass parameters, including; voltage, current
and frequency in a graphical format. In addition, the battery display shows runtime remaining. In a parallel
system, meters for the local UPS and the other UPS in the system can be viewed.
Controls
Allows selection of operating mode, normal, bypass, charger on/off and power module on/off. The EAA
controls screen can be used to enable and disable installed Energy Advantage Architecture options.
Settings
Allows configuration of the unit including meters format, ESS configuration, backlight adjustments, display
contrast, date and time information, serial communication port configuration and display of firmware revision
numbers.
Touch an icon on the Navigation Menu to open the applicable screen.
UPS Operating Instructions