140 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
1100..22..22 UUPPSS OOuuttppuutt
UPS Output Capacity 100% rated current
Output Voltage Regulation ±1.0% (10% to 100% load)
Output Voltage (Nominal +/–3%)
480 Vac nominal, adjustable from 466 Vac to 494 Vac
Output Voltage Harmonic Content 1% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current See Table 5
Output Voltage Balance 2.5% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement ±4° for 100% maximum load imbalance (linear load)
Output Transients Meets Class 1 IEC 62040-3 (10% to 100% load)
Frequency Regulation ±0.1 Hz free running
Synchronous to Bypass +10% to -10%
Frequency Slew Rate .7 Hz per second maximum
Load Compatibility 0.7 pF Leading
0.7 pF Lagging
Overload Capability (kVA or kW)
110% for 10 minutes
125% for 120 seconds
150% for 300 seconds
NOTE The 125% and 150% overloads are based on the non-derated hardware capability of the UPS.
1100..22..33 UUPPSS EEnnvviirroonnmmeennttaall
Operating Temperature 0 to 40°C (32 to 104°F) at elevation up to 1000m without derating. The recommended
operating temperature is 25°C (77°F).
Operating Altitude Maximum 1000 m (3300 ft) at 40°C without derating
Storage Temperature –20 to +50°C excluding batteries (prolonged storage above 40°C causes rapid battery
self-discharge)
Relative Humidity (operating and
storage)
5% to 95% maximum non-condensing.
Acoustical Noise 73dB at a 1m distance, A weighted for one UPS 100% Load.
EMI Emissions and Immunity Meets IEC 62040-2, category C3.
Electrostatic Discharge (ESD)
Immunity
IEC61000-4-2 Level 3 - 4kV contact/ 8kV air discharge.
Product Specifications