Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01 15
• The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
• The cabinet can be installed in line-up-and-match or standalone configurations.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the maximum weight requirements shown in Table 2
and the size requirements shown in Figure 3 through Figure 10. Dimensions are in millimeters (inches).
Table 2 includes the weights of the heaviest cabinet configuration. Actual weights may be less due to the
installed configuration. Weights are in kilograms (pounds).
Table 2. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight kg (lb)
Shipping
Installed
Eaton 9395XC-1500/1500 HD
UPS (Total) 4653.40 (2110.4) 4369.2 (1981.5)
ISBM/PM 3668.5 (1663.7) 3533.5 (1602.5)
I/O 985.0 (446.7) 835.7 (379.0)
Eaton 9395XC-1500/1500 LD
UPS (Total) 4862.0 (2205.0) 4577.8 (2076.1)
ISBM/PM 3668.5 (1663.7) 3533.5 (1602.5)
I/O 1193.6 (541.3) 1044.4 (473.6)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in Table 3. Dimensions are in
millimeters (inches).
Table 3. UPS Cabinet Clearances
From Top of Cabinet 457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
None Required
From Right Side of Cabinet None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
• Recommended Operating Range: 20–25º C (68–77º F)
• Maximum Relative Humidity: 95%, non-condensing
NOTE If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet
environmental requirements supercede the UPS requirements. Operating temperatures
above the recommended range will result in decreased battery life and performance,
and will reduce or void the battery warranty. Refer to Eaton’s Terms and Conditions of
Sale with Battery Replacement Coverage and the Battery Replacement Price Book for
more information. These documents can be found at www.eaton.com/ powerquality or
contact an Eaton service representative to obtain copies.
UPS Installation Plan and Unpacking