Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01 31
Table 10. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part Size
Quantity
Manufacturer Part Number Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts 54862BE
Copper wire
only
3/0 AWG Thomas & Betts
54864BE
4/0 AWG Thomas & Betts 54866BE
250 MCM Thomas & Betts
54868BE
300 MCM Thomas & Betts 54870BE
350 MCM Thomas & Betts 54872BE
400 MCM Thomas & Betts
54874BE
500 MCM Thomas & Betts 54876BE
Manual Hydraulic Crimp Tool 14 Ton
1
Thomas & Betts TBM14M
Die Set
N/A
1
Thomas & Betts
15506
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 11 for conduit
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Ground must be run
in the same conduit as the phase conductors.
Conduit is sized to accommodate one ground conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.