32 Eaton 9395XC UPS 1200kW/1200kVA, 1350kW/1350kVA or 1500kW/1500kVA 164001079—Rev 01
Table 11. 480V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number
of
Conduits
Eaton 9395XC-1200/1200
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 8
AC Output
(A, B, C, Ground)
4 3 6
AC B ypass
(A, B, C, Ground)
4 3 6
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
3 2.5 9
Eaton 9395XC-1350/1350
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 9
AC Output
(A, B, C, Ground)
4 3 8
AC B ypass
(A, B, C, Ground)
4 3 9
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
3 2 12
Eaton 9395XC-1500/1500
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 9
AC Output
(A, B, C, Ground)
4 3 8
AC B ypass
(A, B, C, Ground)
4 3 8
DC (Common
Battery)
Battery
(Positive, Negative, Ground)
3 2.5 12
Battery Conductor Routing: Refer to the notes at the bottom of Table 5 Input/Output Ratings and External
Wiring Requirements. External overcurrent protection and disconnect are not provided by this product, but are
required by codes. Refer to Table 5
If an output lockable disconnect is required, it is to be supplied by the customer.
UPS Installation Plan and Unpacking

Table of Contents