Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual 9-1
Chapter 9 Product Specications
9.1 Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
9.2 Specications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
Models Power Rating Frequency description
93E-15UI-N-64×9Ah-MBS 15 kVA 50/60 Hz
N- Normal type with single feed
I- Internal battery can be selected
0-without battery for internal battery type
T-Transformer UPS
MBS-with internal MBS
U-upgradable
93E-15UI-N-0-MBS 15 kVA 50/60 Hz
93E-15U-N-MBS 15 kVA 50/60 Hz
93E-15UT-N-MBS 15 kVA 50/60 Hz
93E-20I-N-64×9Ah-MBS 20 kVA 50/60 Hz
93E-20I-N-0-MBS 20 kVA 50/60 Hz
93E-20-N-MBS 20 kVA 50/60 Hz
93E-20T-N-MBS 20 kVA 50/60 Hz
93E-30I-N-96×9Ah-MBS 30 kVA 50/60 Hz
93E-30I-N-0-MBS 30 kVA 50/60 Hz
93E-30-N-MBS 30 kVA 50/60 Hz
93E-30T-N-MBS 30 kVA 50/60 Hz
93E-40I-N-128×9Ah-MBS 40 kVA 50/60 Hz
93E-40I-N-0-MBS 40 kVA 50/60 Hz
93E-40-N-MBS 40 kVA 50/60 Hz
93E-40T-N-MBS 40 kVA 50/60 Hz
93E-60-N-MBS 60 kVA 50/60 Hz
93E-60T-N-MBS 60 kVA 50/60 Hz
93E-80-N-MBS 80 kVA 50/60 Hz
93E-80T-N-MBS 80 kVA 50/60 Hz
9.2.1 UPS Environmental
Operating Temperature
UPS: 0 to 40°C (32 to 104°F) without derating. The recommended operating
temperature is 25°C (77°F).
Battery: 5—25°C
Operating Altitude
Maximum 1000m (3300 ft) at 30°C without derating
Storage Temperature
-15 to +55°C, excluding batteries (prolonged storage above 40°C causes
rapid battery self-discharge)
Relative Humidity (operating and storage)
5% to 95% maximum noncondensing
Acoustical Noise
≦
55 dB (15-20 kVA)
≦
62 dB (30-40 kVA)
≦
65 dB (60-80 kVA)
at a 1m distance, per ISO 7779
EMC
Meets IEC 62040-2 2005 C3