UPS Installation Plan and Unpacking
3-4 Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-4.
Table 3-4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model Model Input / Output Voltage
Heat Rejection
BTU/hr x1000 (kg-cal/hr)
93E-15UI-N-64×9Ah-MBS 15 kVA 380/380 400/400 415/415 862
93E-15UI-N-0-MBS 15 kVA 380/380 400/400 415/415 862
93E-15U-N-MBS 15 kVA 380/380 400/400 415/415 862
93E-15UT-N-MBS 15 kVA 380/380 400/400 415/415 1306
93E-20I-N-64×9Ah-MBS 20 kVA 380/380 400/400 415/415 1149
93E-20I-N-0-MBS 20 kVA 380/380 400/400 415/415 1149
93E-20-N-MBS 20 kVA 380/380 400/400 415/415 1149
93E-20T-N-MBS 20 kVA 380/380 400/400 415/415 1743
93E-30I-N-96×9Ah-MBS 30 kVA 380/380 400/400 415/415 1723
93E-30I-N-0-MBS 30 kVA 380/380 400/400 415/415 1723
93E-30-N-MBS 30 kVA 380/380 400/400 415/415 1723
93E-30T-N-MBS 30 kVA 380/380 400/400 415/415 2612
93E-40I-N-128×9Ah-MBS 40 kVA 380/380 400/400 415/415 2298
93E-40I-N-0-MBS 40 kVA 380/380 400/400 415/415 2298
93E-40-N-MBS 40 kVA 380/380 400/400 415/415 2298
93E-40T-N-MBS 40 kVA 380/380 400/400 415/415 3482
93E-60-N-MBS 60 kVA 380/380 400/400 415/415 3447
93E-60T-N-MBS 60 kVA 380/380 400/400 415/415 5224
93E-80-N-MBS 80 kVA 380/380 400/400 415/415 4596
93E-80T-N-MBS 80 kVA 380/380 400/400 415/415 6965