UPS System Installation
4-12 Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
6. Route and install pull chain wiring (Twisted Wires 0.5-2.0 mm
2
) between the UPS cabinets and cabinet
MOBs. See Figure 4-7, Figure 4-10 and Figure 4-11 for wiring information.
7. If wiring Mini-Slot connections, proceed to paragraph 4.5.3;
4.5.3 Installing Mini-Slot Interface Connections
For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8)
To install wiring:
1. If not already installed, install the LAN drop.
2. Route and install the LAN and other cables to the appropriate Mini-Slot cards. See Figure 4-6 and Figure 4-7
for Mini-Slot communication bay locations.
3. Refer to the manual supplied with the Mini-Slot card for operator instructions.
4. Install the power terminal cover using the provided hardware.
LAN drop for connection to UPS communications card is to be supplied by customer.
NOTE