UPS Installation Plan and Unpacking
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual 3-19
Table 3-7. Recommended Input Circuit Breaker Ratings
93E-15
80% Derated 29A
100% Rating 23A
93E-20
80% Derated 38A
100% Rating 31A
93E-30
80% Derated 57A
100%Rating 46A
93E-40
80% Derated 77A
100% Rating 61A
93E-60
80% Derated 115A
100% Rating 92A
93E-80
80% Derated 153A
100% Rating 123A
Circuit Breaker Rating
UPS Model Load Derating 400V
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table 3-7 in accordance with local regulations.
Table 3-8. Recommended Bypass and Output Circuit Breaker Ratings
Circuit Breaker Rating
UPS Model Load Derating 400V
93E-15
80% Derated
27A
100% Rating
22A
93E-20
80% Derated
36A
100% Rating
29A
93E-30
80% Derated
54A
100% Rating
43A
93E-40
80% Derated
72A
100% Rating
58A
93E-60
80% Derated
108A
100% Rating
87A
93E-80
80% Derated
144A
100% Rating 115A
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in Table 3-5. The recommended line-to-line load unbalance is 50% or less.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the recommended rating for bypass
and output circuit breakers.