UPS System Installation
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual 4-9
Figure 4-7. Interface Terminal Detail (Terminal Cover Removed)
Figure 4-8. Building Alarm Terminal Block Connector Assignments
Table 4-1. Building Alarm Connections
Building Alarm Terminal Name Description
1 Building Alarm 1 +
Input: Programmable UPS alarm, activated by a remote dry contact closure.
2 Building Alarm 1 –
3 Building Alarm 2 +
Input: Programmable UPS alarm, activated by a remote dry contact closure.
4 Building Alarm 2 –
5 Building Alarm 3 +
Input: Programmable UPS alarm, activated by a remote dry contact closure.
6 Building Alarm 3 –
93E 60-80 kVA93E 15-40 kVA
Building Alarm 1
Building Alarm 3
Building Alarm 2
Mini-Slot Communication Bay 1
Mini-Slot Communication Bay 1
Mini-Slot Communication Bay 2
Mini-Slot Communication Bay 2
REPO Terminals (See Figure 4-13 for Detail)
REPO Terminals (See Figure 4-13 for Detail)
Parallel CAN Output (RJ45)
Parallel CAN Output (RJ45)
Pull chain Terminals
Pull chain Terminals
Parallel CAN Input (RJ45)
Parallel CAN Input (RJ45)
Building Alarm (See Figure 4-8 for Detail)
Building Alarm (See Figure 4-8 for Detail)