The UPS ventilation requirements are shown in Table 4.
Table 4. Air conditioning or ventilation requirements during full load operation
Model
kVA
Input /
output
voltage
Heat
rejection
(kW)
Heat
rejection
(BTU/hr)
Eaton 93E-15UI-N-64×9Ah-MBS
15
380/380
400/400
415/415
0.84
2 853
Eaton 93E-15UI-N-0-MBS
15
380/380
400/400
415/415
0.84
2 853
Eaton 93E-20I-N-64×9Ah-MBS
20
380/380
400/400
415/415
1.33
4 527
Eaton 93E-20I-N-0-MBS
20
380/380
400/400
415/415
1.33
4 527
Eaton 93E-30I-N-96×9Ah-MBS
30
380/380
400/400
415/415
1.84
6 293
Eaton 93E-30I-N-0-MBS
30
380/380
400/400
415/415
1.84
6 293
Eaton 93E-40I-N-128×9Ah-MBS
40
380/380
400/400
415/415
2.49
8 513
Eaton 93E-40I-N-0-MBS
40
380/380
400/400
415/415
2.49
8 513
Eaton 93E-60-N-MBS
60
380/380
400/400
415/415
3.57
12 181
Eaton 93E-80-N-MBS
80
380/380
400/400
415/415
4.57
15 593