Type Article No Nominal battery
voltage
12V VRLA
Blocks
With 93PS
30–40 kW
NZM1–A160 281234
(P-122000199)
336–432 V 28–36
NZMN2-A160 259092 444–480 V 37–40
NOTE: Maximum string length for the 93PS C-model is 36 blocks, 216 cells (432 V)
Note: Contact your Eaton sales representative for more information about the
circuit breakers, or if you need help choosing the right model for your UPS
system.
Use the following 24 V shunt release with early-make auxiliary contact together
with the above circuit breakers:
Type Article No
NZM1-XAHIVL24AC/DC 259792
(P-152001062)
Note: In 93PS UPS C-model, the internal and external circuit breakers
function in cooperation with each other.
Table 10: Rated and maximum currents for rated power and voltage
Rectifier input UPS output / bypass Battery
Rated
power
[kW]
Rated
voltage
[V]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
8 380 13 15 12 18 22 26
400 12 14 12 17 22 26
415 12 14 11 16 22 26
10 380 16 19 15 22 27 33
400 15 18 15 21 27 33
415 15 17 14 20 27 33
15 380 24 28 23 34 41 49
400 23 27 22 32 41 49
415 22 26 21 31 41 49
20 380 32 37 31 45 55 66
400 30 36 29 42 55 66
415 29 34 28 41 55 66
Eaton 93PS UPS 8–40 kW User's and installation guide
©
Eaton Corporation plc 2016. All rights reserved. Revision: 003 Document ID: P-164000493 41 (104)