Rectifier input UPS output / bypass Battery
Rated
power
[kW]
Rated
voltage
[V]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
Rated
current
[A]
Maximum
current
[A]
30 380 48 56 46 67 82 98
400 45 53 44 64 82 98
415 44 51 43 61 82 98
40 380 64 75 62 89 110 131
400 60 71 59 85 110 131
415 58 69 57 82 110 131
Notes:
1. Maximum rectifier current calculated at the -15% voltage tolerance and 102% con-
tinuous overload.
2. Maximum output/bypass current calculated at continuous 125% overload and at
-15% voltage tolerance.
3. Maximum battery current calculated at rated load and 1.67 V cell voltage for the
default 32 block string length.
Eaton 93PS UPS 8–40 kW User's and installation guide
©