EasyManua.ls Logo

Eaton 93PS - UPS Environmental Specifications

Eaton 93PS
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Load power factor (permitted range) From 0.8 lagging to 0.8 leading
Max ambient temperature without de-rating 40 °C
9.5 UPS environmental specifications
Table 32: UPS environmental specifications
Acoustic noise at 1 m 40 kW unit: <55 dB at 75% load
40 kW unit: <60 dB at 100% load
Temperature range, operation
Recommended range*
0–40 °C
+20–25 °C
Temperature range, storage and
transportation
-25–+55 °C
Relative Humidity
Recommended range*
5–95 %
20–60 %
Condensation No
Operating altitude 1000 m without derating
Up to 2000 m with derating
Maximum storage time with internal
batteries
6 months without recharge
Over voltage category OVC II
Pollution degree 2
*) Note: For maximum lifetime for UPS and batteries, keep the environment in the
recommended range.
© Eaton Corporation plc 2020. All rights reserved. Revision: 006 Document ID: P-164000493 116
(126)
Eaton 91PS/93PS UPS 8–40 kW User’s and Installation Guide

Table of Contents

Other manuals for Eaton 93PS

Related product manuals