Table 20: 91PS rated and maximum currents for rated power and voltage (3-
phase input, 1-phase output models)
Rectifier input UPS output
/ bypass
Battery
Rated
power [kW]
Rated
voltage [V]
Rated
current [A]
Maximum
current [A]
Rated
current [A]
Rated
current [A]
8 380 18 18 36 22
400 17 18 35 22
415 17 18 33 22
10 380 21 22 45 28
400 20 22 43 28
415 19 22 42 28
15 380 29 29 68 42
400 28 29 65 42
415 27 29 63 42
20 380 38 38 91 55
400 36 38 87 55
415 35 38 83 55
30 380 57 57 136 83
400 54 57 130 83
415 52 57 125 83
Notes:
1. Maximum rectifier current calculated at the minimum voltage tolerance.
© Eaton Corporation plc 2020. All rights reserved. Revision: 006 Document ID: P-164000493 48 (126)
Eaton 91PS/93PS UPS 8–40 kW User’s and Installation Guide