EasyManuals Logo

Eaton 9E-IN 2K XL User Manual

Eaton 9E-IN 2K XL
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
-27-
Figure 7.1 Setting by LCD
To exit the setting mode that requests a pressing once on the “Enter” button;
to continue setting, press “Select” button. If no any pressing on the Select”
or “Enter” button lasting for more than 10 seconds, the setting mode will exit
automatically.
The output frequency string OPF”, Bypass status string bYPA”, operating
mode string MOdE”, External Battery Ah “EbAH”, battery remaining time
string “bATT”(only for 1K/2K/3K) , Charger current string”CHG” would be
presented circularly. The only one voltage value can be selected in “220V”,
“230V”, 240V” (for 1K/2K/3K) or “200”,“208V”, “220V”, “230V”, “240V” (for
1KXL/2KXL/3KXL) at any time; The only one frequency value can be
selected in 50Hz”, “60Hz” at any time; Bypass status can be selected in
“000” or “001”(Here 000 means Bypass Disable,001 means Bypass
Enable),The UPS would turn to bypass mode in several seconds if “Bypass
Enable” is selected, and turn to no output mode in several seconds if
“Bypass Disable” is selected; Operating mode can be selected in “UPS”,
“ECO”, CVF”(Here UPS” means the normal online mode, ECO” means
the high efficiency mode, and “CVF” means the converter mode), The mode
change would be active only after the UPS is turned on; External Battery Ah
could be selected from “005” to 300”(Here “005” means 5Ah total external
battery); Charger Current could be selected 002/004/006/008/010 for
1KXL and 001-010 for 2KXL/3KXL (Here 001 means 1A charger). For
1K/2K/3K, the battery remaining time function could be selected in “000” or
“001”. (Here 000 means battery remaining time function is disabled, then the
battery remaining time could not display on LCD in battery mode. 001
means battery remaining time function is enabled, then in battery mode or
battery test mode the battery remaining time (in unit Min or Sec) and string
“bATT” would display on LCD in turn every 2s).