10 Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
Table 6. User Settings (Continued)
Submenu Available Settings Default Settings
[Timer] [10min] … [120min] [90min]
If Disabled, LCD and communication will turn OFF
immediately after UPS is OFF.
If Enabled, LCD and communication stays ON 1h30
min after UPS is OFF.
Site wiring fault
[Enabled] [Disabled] [Disabled]
Prevents from starting the UPS in case of phase vs
neutral wires swapping.
Power Off alert
[Enabled] [Disabled] [Enabled]
If Enabled, activates a confirmation screen that
requires user confirmation after pressing the
power button, before the UPS shutdown occurs.
Battery Settings
Low battery warning
[Capacity] [0%] … [100%] [0%]
[Runtime] [0min] … [60min] [3min]
The alarm triggers when the set percentage of
battery capacity or remaining back-up time is
reached.
Restart bat. level
[0%] ... [100%] [0%]
If set, automatic restart will occur only when
percentage of battery charge is reached.
Com Settings Input signals
[ROO] [RPO] [DB9–4}
Sets Input signals parameters (function, delay,
operation) through external contact connectors or
RS232.
ROO port:
- [Function]: [No] [ROO] [RPO] [Building alarm]
[Forced bypass] [On generator] [Remote shutdown]
[No]
- [Delay]: [0s] … [999s] [0s]
- [Active]: [Open] [Closed] [Closed]
RPO port:
- [Function]: [No] [ROO] [RPO] [Building alarm]
[Forced bypass] [On generator] [Remote shutdown]
No
- [Delay]: [0s] … [999s] [0s]
- [Active]: [Open] [Closed] [Open]
DB9-4 port: No
- [Function]: [No] [ROO] [RPO] [Building alarm]
[Forced bypass] [On generator] [Remote shutdown]
User Settings