11. Specifications
Table 6. Electrical output
All models Normal mode Battery mode
Voltage regulation ±2% (Lx-N); ±5% (L1-L2) ±10%
Efficiency > 97% (High Efficiency mode)
94% for 9PX8KSP/9PX10KSP (Typical)
Frequency regulation Sync with line ±5% of nominal line
frequency (outside this range: ±0.5%
of auto-selected nominal frequency)
±0.5% of auto-selected nominal
frequency
Nominal output 100/200V, 110/220V, 115/230V, 120/208V, 120/240V, 127/220V (voltage
configurable) (Output Rating are in Table1 of 9.1 section)
Frequency 50 or 60Hz, autosensing or configurable as a frequency converter
Output overload 100-102%: no alarm
102-110%: load transfers to Bypass
mode after 2 minutes
110-125%: load transfers to Bypass
mode after 1 minute
125-150%: load transfers to Bypass
mode after 10s
> 150%: load transfers to Bypass
mode after 900ms
100-102%: no alarm
102-130%: load transfers to
Bypass mode after 10s
> 130%: load transfers to Bypass
mode after 100ms
Output overload
(Bypass mode)
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Voltage waveform Sinewave
Harmonic distortion < 3% THDV on linear load
< 5% THDV on non-linear load
Transfer time Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor 0.9
Load crest ratio 3 to 1
Table 7. Electrical output connections
Model Output connection
9PX8KSP,
9PX10KSP
Hardwired
(2) L14-30R outlets
(1) L6-30R outlet
Table 8. Environmental and safety
EMC certifications UL 1778 4th
CAN/CSA C22.2 No 107.3-05 Ed.2
EMC (Emissions)* FCC part 15 Class A
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
EMC (Immunity) IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4