Page 45
614-00205-01_EN
ENGLISH
11. Specifications
Agency markings CE / cULus / NOM
Operating temperature 32 to 104°F (0 to 40°C) in Online mode, with linear derating for altitude
Note: thermal protection switches load to Bypass in case of overheating.
Storage temperature 32 to 104°F (0 to 40°C) with batteries
5 to 140°F (-15 to 60°C) without batteries
Transit temperature -4 to 122°F (-20 to 50°C)
Relative humidity 0 to 95% no condensing
Operating altitude Up to 2,000 meters (6,562 ft) above sea level with 10% derating per 1000m
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise < 55 dBA at 1 meter typical
Table 9. Battery
Internal batteries EBM
Rack / Tower
configuration
9PX8KSP/9PX10KSP: 360Vdc
(±180Vdc)
9PXEBM360SP: 360Vdc (±180Vdc)
Type
CSB/HR1227WF2FR
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year
float service life at 77°F (25°C).
Lifetime is reduced above 86°F (30°C).
Monitoring Advanced monitoring for earlier failure detection and warning
Battery port External three-pole SBS75G Brown + SBS75G White connectors on UPS for
connection to EBM
EBM battery cable
length
9PXEBMSP360: 50cm (19.7in)
Table 10. Communication options
Communication bay (1) available independent communication bay for connectivity cards
Compatible connectivity
cards
Network-MS
Modbus-MS
Relay-MS
Communication ports RS-232 (DB9): 1200-19200 bps
USB: 19200 bps
Relay output contacts (4) relay outputs (normally open or normally closed)
Remote On/Off 2 pins jumper (normally closed)
Remote Power Off 3 pins jumper (pin 1 & 3 normally closed)