EasyManua.ls Logo

Eaton C441R - Page 41

Eaton C441R
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 79. Assembly Instance 141 (0x8D): Full S811 Monitoring,
Current in 0.1A (Cont.)
Byte
Offset
Word
Offset
Size
(bytes) Name Description
36 18 2 Motor
Control
Warnings
S811+ Motor Control Warning Bit Field
Bit Warning
0 Phaseloss
1 Phase Imbalance
2 Thermal Pile
3 Overcurrent
4 Breaker Fault
5 GND Fault
6 Motor Stall
7 Motor Jam
8 OverTemp
9 UnderLoad
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Other
38 19 6 Active Fault
List
Will display up to 3 faults/warnings that
are actively present
44 22 4 Total Motor
Starts
Number of motor starts
Total Assembly Size (bytes): 48
Table 79. Assembly Instance 141 (0x8D): Full S811 Monitoring,
Current in 0.1A
Includes the most common measurement values. Current values scaled in 0.1A
Word Size (bytes): 2
Byte
Offset
Word
Offset
Size
(bytes) Name Description
0 0 2 Device
Status
Device Status Bit Array
0 Running - RUN command active
1 Jogging - Jog command active
2 Permissive - Start allowed (must be 1
to start)
3 Ramp2 - Ramp2 settings active
4 Local Control (0 - network; 1 - local)
5 Faulted - S811+ fault present
6 Warning - S811+ warning present (self
clearing)
7 In bypass - S811+ Bypass closed
8 = Output 1
9 = Output 2
10 = Input 1
11 = Input 2
12 = Input 3
13 = Input 4
14 = Alarm No Trip Enabled
15 = S811+ Internal Comm Loss
2 1 6 3Ph RMS
Line Current
(deciamps)
Scaled RMS 3phase line current - This is
the actual current flowing to the motor in
0.1A.
8 4 2 3Ph Ave
Line Current
(deciamps)
Scaled RMS average of the 3phase line
current - This is the actual current flowing
to the motor in 0.1A.
10 5 2 Average
current as %
FLA
Average of the 3 phase current as a per-
centage of the Motor Nameplate fla setting
12 6 1 % Thermal
Pile used
Thermal Pile Used Percentage - Trip at
100%
14 7 6 3Ph RMS
Mains
Voltage
3 Phase RMS Mains voltage reading (in
volts)
20 10 2 Ave 3Ph
Real Power
(kW)
Average 3 phase real power (in kW)
22 11 2 Power Factor Power factor reading 0 - 1.0000 (in 0.0001)
24 12 1 Field Inputs A bitfield representing the input points.
Bit = Description
0 = Input 1
1 = Input 2
2 = Input 3
3 = Input 4
26 13 6 Power Pole
Temperature
S811+ power pole temperature in 0.1
degrees C
32 16 2 Line
Frequency
Frequency reading of incoming mains volt-
age (in 0.01Hz)
34 17 2 Motor
Control
Faults
S811+ Motor Control Fault Bit Field
Bit Fault
0 Phaseloss
1 Phase Imbalance
2 Thermal Pile
3 Overcurrent
4 Breaker Fault
5 GND Fault
6 Motor Stall
7 Motor Jam
8 OverTemp
9 UnderLoad
10 Reserved
11 Estop
12 Reserved
13 Reserved
14 Reserved
15 Other

Related product manuals