User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 85. Class 44 (0x2C): Overload Object (Cont.)
Attrib NV Access
Data
Type Name Description
119
(0x77)
NV Set/Get USINT Phase Loss
Trip Enable
Motor phase loss trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
120
(0x78)
NV Set/Get USINT Motor Phase
Loss Trip
Level
Current phase loss trip threshold
121
(0x79)
NV Set/Get UINT Motor
Phase Loss
Duration
Amount of time a phase loss condi-
tion must exist before a trip; 0.0
- 60.0 (in 0.1secs)
122
(0x7A)
NV Set/Get USINT Phase
Imbalance
Trip Enable
Current phase imbalance trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
123
(0x7B)
NV Set/Get USINT Motor Phase
Imbalance
Trip Level
Current imbalance trip threshold
124
(0x7C)
NV Set/Get UINT Motor Phase
Imbalance
Trip Duration
Amount of time a current imbalance
condition must exist before a trip;
0.0 - 60.0 (in 0.1secs)
125
(0x7D)
NV Set/Get USINT Ave Power
Trip Enable
Average power trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
126
(0x7E)
NV Set/Get UINT Ave Power
Low Trip
Threshold
Low power trip threshold (in percent
of rated W)
rated W = sqrt(3)*0.8PF*motor
fla*rated motor voltage
127
(0x7F)
NV Set/Get UINT Ave Power
High Trip
Threshold
High power trip threshold (in per-
cent of rated W)
rated W = sqrt(3)*0.8PF*motor
fla*rated motor voltage
128
(0x80)
NV Set/Get UINT Ave Power
Trip Duration
Amount of time a low or high power
condition must exist before a trip;
0.0 - 60.0 (in 0.1secs)
Table 86. Class 45 (0x2D): Softstart Object
Instance Count: 1
Instance List: 1
Attrib NV Access
Data
Type Name Description
3
(0x03)
V Get BOOL At Ref Indicates whether the softstart is
in bypass or not.
4
(0x04)
NV Set/Get USINT Soft Start
Method
Selects the ramp start method.
1=Voltage Ramp (no current limit)
2=Current Limit (no voltage ramp)
100=Pump start
7
(0x07)
NV Set/Get UINT Start Ramp
Time
Motor start ramp time.
8
(0x08)
NV Set/Get USINT Initial
Starting
Torque
Starting torque setting for ramp
start
11
(0x0B)
NV Set/Get BOOL Expected
Incoming
Phase
Sequence
Expected phase sequence of
incoming mains
0 - ABC
1 - ACB
16
(0x10)
NV Set/Get UINT Stop Ramp
Time
Motor stop ramp time. Parameter
is not active when start method is
set to pump
100
(0x64)
NV Set/Get UINT Pump Stop
Time
The amount of time to use for
the pump stop ramp behavior.
Parameter is active when pump-
start is selected for motor start
method
101
(0x0D)
NV Set/Get USINT Kickstart
Duration
The amount of time to apply a
kick start
0.0 - 2.0 (in 0.1secs)
102
(0x0E)
NV Set/Get USINT Kickstart
Starting
Torque
Initial torque value for the kick
start
103
(0x65)
NV Set/Get USINT Ramp2
Soft Start
Method
Selects the ramp2 start method.
1=Voltage Ramp (no current limit)
2=Current Limit (no voltage ramp)
100=Pump start
104
(0x66)
NV Set/Get UINT Ramp2 Start
Ramp Time
Motor start ramp time for ramp2.
105
(0x67)
NV Set/Get USINT Ramp2 Initial
Starting
Torque
Starting torque setting for ramp2
start
106
(0x68)
NV Set/Get BOOL Ramp2
Expected
Phase
Sequence
Expected phase sequence of
incoming mains for ramp2 start
1 - ACB
107
(0x69)
NV Set/Get USINT Ramp2
Kickstart
Duration
The amount of time to apply a
kick start
0.0 - 2.0 (in 0.1secs) for ramp2
start
108
(0x6A)
NV Set/Get USINT Ramp2
Kickstart
Starting
Torque
Initial torque value for the kick
start for ramp2
109
(0x6B)
NV Set/Get UINT Ramp2 Stop
Ramp Time
Motor stop ramp time for ramp2.
Parameter is not active when
ramp2 start method is set to pump
110
(0x6C)
NV Set/Get UINT Ramp2 Pump
Stop Time
The amount of time to use for
the pump stop ramp2 behavior.
Parameter is active when pump-
start is selected for ramp2 motor
start method
111
(0x6D)
V Get INT Power Pole
Temperature
S811+ power pole temperature in
0.1 degrees C
112
(0x6E)
V Get INT Power Pole
Temperature
S811+ power pole temperature in
0.1 degrees C
113
(0x6F)
V Get INT Power Pole
Temperature
S811+ power pole temperature in
0.1 degrees C