EasyManua.ls Logo

Eaton Cutler-Hammer Digitrip 1150 - Page 18

Eaton Cutler-Hammer Digitrip 1150
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Effective 10/2004
Page 18
I.L. 70C1036H05
Figure 2.8 Zero Sequence Sensing Scheme for Standard Circuit Breaker
Figure 2.9 Multiple Source/Multiple Ground Scheme
If the breaker is removed
from cell (B-6,B-7) jumper disconnected, Residual Ground settings will apply.
1
2
3
4
R
5
R
5
R
5
φ
φ
T
M2
M1
B5
B4
I/2
G
I/2
G
I/2
G
I/2
G
I
G
I
G
i
g
i
g
i/2
g
i/2
G
i/2
g
i/2
g
i/2
g
Neutral Sensors Wired
in a Loop Configuration
B5
B5
B4
B4
N
N
Internal
Digitrip
Sensor
Breaker M2 trips since this is the only breaker seeing the I fault via element R .
No jumper on B-6, B-7 terminals - all breakers are programmed for standard Residual Ground Fault
protection.
AUX CTs not shown. Wiring needed at system level is shown as a dotted line.
Capital letters represent primary current. Lowercase letters represent secondary current.
The three breakers (M1, M2, and T) must all have the same breaker/sensor rating.
G5
Notes:
Courtesy of NationalSwitchgear.com

Table of Contents

Other manuals for Eaton Cutler-Hammer Digitrip 1150

Related product manuals