Effective 10/2004
Page 3I.L. 70C1036H05
Table 1.1a CURRENT Protection Functions for Digitrip 1150/1150i Trip
Notes: 1. ANSI/UL versions are limited to 1200 Amperes to comply with UL and NEC standards.
2. Four cause of trip LEDs indicate LONG, SHORT, INST or GROUND trip. Making Current Release and the
separate High Instantaneous Module are indicated by the Instantaneous LED.
3. An additional setting is marked M1 where:
Standard Circuit Breaker M1 = 14 x In for Plug Amps 100 through 1250A
M1 = 12 x In for Plug Amps 1600, 2000, 2500A
M1 = 10 x In for Plug Amps 3000, 3200A
Double Wide Circuit Breaker M1 = 14 x In for Plug Amps 2000, 2500A
M1 = 12 x In for Plug Amps 3000, 3200, 4000, 5000A (see Section 2.5)
M1 = 10 x In for Plug Amps 6000A, 6300A
4. Only available when Long Time I
2
T is selected.
5. Phase protection with 3 TRIP response types (See Section 4.2.1).
Trip Unit Type Digitrip 1150 Digitrip 1150i
Ampere Range 100A-6000A 200A-6300A
RMS Sensing Yes Yes
Protection and Coordination
Protection Ordering Options Catalog #
Fixed Rating Plug (I
n
)
OverTEMPerature TRIP
Curve Type
SLOPE
11LSI, 11LSIG, 11LSIA or
11PLSI, 11PLSIG, 11PLSIA
Yes
Yes
LSI/LSIG, LSIA
I2T, I4T
IEEE
5
11IEC, 11IEC-EF or
11PIEC, 11PIECEF
Yes
Yes
LSI/LSIG
I2T, I4T
IEC
5
Long LONG delay Pick Up
Delay LONG delay TIME @ 6 x (I
r
) I2T
Protection LONG delay TIME @ 6 x (I
r
) I4T
LONG delay thermal MEMORY
0.4-1.0 x (I
n
)
2-24 seconds
1-5 seconds
Yes
0.4-1.0 x (I
n
)
2-24 seconds
1-5 seconds
Yes
SHORT delay Pick Up
3
Short
Delay SHORT delay TIME @ 8 x (I
r
) I2T
4
Protection SHORT delay TIME FLAT
SHORT delay TIME ZONE INTERLOCK
150-1000% or 1200% or 1400% x
(I
r
)
0.10-0.50 s
0.10-0.50 s
Yes
150-1000% or 1200% or 1400% x (I
r
)
0.10-0.50 s
0.10-0.50 s
Yes
Instan- INSTantaneous Pick Up
taneous
Protection Off setting
Making Current Release
200-1000% x or 1200% or 1400%
(I
n
)
Yes
Yes
200-1000% or 1200% or 1400% x (I
n
)
Yes
Yes
Neutral 4
th
Pole or External Neutral Trip
Protection
Yes-CAT # LSI only
(50%,100%)
Yes-CAT # IEC only
(50%,100%)
Ground GROUND fault option
(Earth) GROUND fault Pick Up
Fault Off Position
Protection GROUND fault delay @ .625 x (I
n
) I2T
GROUND fault delay FLAT
GROUND fault ZONE INTERLOCK
GROUND fault memory
Yes
24-100% x (I
n
)
1
No
0.10-0.50 s
0.10-0.50 s
Yes
Yes
Yes
10-100% x (I
n
)
Yes
0.10-0.50 s
0.10-0.50 s
Yes
Yes
Phase Protection
AMP UNBALANCE
PHASE LOSS (current-based)
Yes
Yes
Yes
Yes
System Diagnostics / Protection Related Alarms
Status/Long Pick Up LED
Cause of Trip LEDās
Yes
Yes
2
Yes
Yes
2
HighLOAD ALARM
Long Delay Pick Up ALARM
GROUND ALARM
GROUND ALARM only
NEUTral AMPere ALARM
OPeration COUNT ALARM
Yes
Yes
Yes-CAT # LSIG
Yes āCAT# LSIA
Yes
Yes
Yes
Yes
Yes- CAT# IECEF
ā
Yes
Yes
Auxiliary Relay Contacts (Programmable)
Block Close (1 contact)
ALARM/TRIP (2 contacts)
Yes
Yes
Yes
Yes